IS 3103 (1975) : Code of Practice for Industrial Ventilation
[CED 12: Functional Requirements in Buildings]
Jawaharlal Nehru
'Step Out From the Old to the New"
aj^&vi iJii^s:y>K^ isb^^ni^seg
:<>5&i| mT'5K^5?::5:^>^i»l
K^^^iXSVCd^
Satyanarayan Gangaram Pitroda
Invent a New India Using Knowledge
Bhartrhari — Nitisatakam
''Knowledge is such a treasure which cannot be stolen"
^'^^^r
k
BLANK PAGE
^*-^^^
PROTECTED BY COPYRIGHT
Indian Standard
IS: 3103 -1975
( Reaffirmed 2004 )
CODE OF PRACTICE FOR
INDUSTRIAL VENTILATION
( First Revision )
Thiid Reprint MAY 1993
UDC 628.83:725.41
@ Copyright W16
BUREAU OF INDIAN STANDARDS
MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002
Gr5 May 1976
15:3103*1975
Indian Standard
CODE OF PRACTICE FOR
INDUSTRIAL VENTILATION
( First Revision )
Functional Requirements in Buildings Sectional Committee, BDC 12
Chairman Representing
Lt -Gen B. N. Das* Ministry of Defence
Members
Additional Dibector Standards Ministry of Railways '
( Architecture )
Joint Director Standards
( Architect ) ( Alternate )
Director Directorate GeHcral of Observatories, New Ejrlhi ^
Director ( Architecture ) Central Public Works Department
ShRIMATi E. S. Ghuman Indian Institute of Architects, Bombay
ShriJ. M. Benjamin [Alternate)
Shri R. G. Gokkale In personal capacity ( Nirman Bkavan, Ntw Delhi )
Shbi J. G. Kapur Danfoss ( India ) Ltd, New Delhi
Shri B. D. Kshirsagar Ministry of Defence
Shbi L. R. Lalla ( Alternate ) "
Shri G. C. Mathur National Buildings Organization
Shri M. M. Mistry ( Alternate )
Db V. Narasimhak Central Building Research Institutc( CSIR }, Roorkee
Shbi M. R. Sharma ( Alternate )
Shbi J. R. Ovalekab National Safety Council, Bombay
Shri N. Raghavan ( Alienate )
Shbi M. M. Pande Voltas Ltd, Bombay
Shbi R. N. Pawar Directorate General of Health Services. New Delhi
ShriS. Purushothama Ministry of Labour, Employment & Rehabilitation,
New Delhi
Prof Rattan Kumar University of Roorkee * *
Shri S. SuBBA Rao All India Institute of Hygiene & Public Health,
Calcutta
Shbi A. V. Rao { Alternate )
Shri Saved S. Shafi Institute of Town Planners, Nt-w Delhi -
Shri D. P. Sharma ( Alternate )
*Also represents the Institution of Engineers ( India ).
( Continued om pa0e2 )
^ Copyright 1976
BUREAU OF INDIAN STANDARDS
This publication is protected under the Indian Copyright' Act [ XtV uf 1957 /and
reproduciion in whole or in part by any means except with written permission ot the
publisher shall be deemed to be an infringement of copyright under the tafd Act.
» ■ '
IS: 3103 -1975
( Continued from page 1 )
Members
Shei R. L. Subi
Shbi D, Ajitha Simha,
Director ( Civ Engg )
Representing
Suri & Suri Consulting Acoustical Engineers,
New Delhi
Director General, ISI ( Ex-offieio Member )
Secretary
ShrI V. KAXYANAStTNDARAM
Assistant Director ( Civ Engg ), ISI
Forced Ventilation ( Industrial ) Subcommittee, BDC 12 : 8
Convener
Shei J. C, Kapur
Members
Shri K. N. Bhar
Shri a. Datta
Surg Cdr M. S. Malhotra
Shri J . G . M anqi«a)7i
Shri H. V. Sharma ( Alternate
Shri Naunihal Singh
Shri Shiv Nath ( Alternate )
Shri S. Pitrushothama
Shri S. Subba Rao
Shri A. V. Rao ( Alternate )
Shri N. Sbshadri
Shri K. Sitbrahamanyam
Danfoss ( India ) Limited, New Delhi
Central Public Works Department
Keymcr, Bagshawc & Co ( India ) Private Ltd,
Calcutta
Ministry of Defence
Air. Conditioning Corporation Ltd, Calcutta
National Physical Laboratory ( GSIR ), New Delhi
Miniitry of Labour Employment & Rehabilitation
All India Institute of Hygiene & Public Health,
Calcutta
India Mcteorcrfogical Department (The Observatory),
New Delhi
Ahmadabad Textile Industry's Research Association,
Ahmadabad
18:3103-1975
Indian Standard
CODE OF PRACTICE FOR
INDUSTRIAL VENTILATION
{ First Revision )
0. FOREWORD
0.1 This Indian Standard ( First Revision ) was adopted by the Indian
Standards Institution on 31 December 1975, after the draft finalized by the
Functional Requirements in Buildings Sectional Committee had been
approved by the Civil Engineering Division Council,
0.2 Due consideration should be given to the ventilation requirements in
designing factories and industrial buildings. Provision for ventilation
becomes necessary for dilution of inside air to prevent vitiation by causes,
such as body odours, to remove contaminants in air released during
manufacturing processes and to maintain satisfactory thermal enviroments.
The application of ventilation should be considered with other measures to
control heat given off during industrial processes. Ventilation by natural
meahs may not be sufficient in certain industries to provide such thermal
environments as will assist the maintenance of heat balance of the body
and to prevent acute discomfort and injury to the health of the workers.
In such cases mechanical ventilation and cooling systems, where neces-
sary, may be employed to achieve satisfactory results. Sortie principles of
industrial ventilation are dealt with in this code in order to give guidance
to those concerned in this field. In the preparatioti of this code, the
requirements of the Factories Act and Rules thereunder have been taken
into consideration.
0.3 This standard covers ventilation of industrial buildings only and was
first published in 1965. The present revision waS taken tip with a view to
incorporate necessary provisions regarding control of heat hazards due to
various processes in the industry. Some of the significant changes made
are given in 0.3.1.
0.3.1 In this code certain new definitions have been a^ded. The range
of recommended capture velocities and the provisions for orientation of
buildings have been included. The design considerations for ventilation,
provisions for mechanical ventilation have been modificdr The require-
ments for ventilation of buildings, natural ventilation and positive ventila-
tion have also been modified.
1$ 13103-1975
0.4. The current practice in this country regarding the threshold limit
values for contaminants ( see 2*21 and 4.5.1 ) is to refer to the latest pub-
lication of the American conference of Governmental Industrial Hygienists.
0.5 For the purpose of deciding whether a particular requirement of^is
standard is complied with, the final value, observed or calculated, express-
ing, the result of a tester analysis, shall be rounded off in accordance with
IS : 2-1960*. The number of^ignificant places retained in the rounded off
value should be the same as that of the specified value in this standard.
1. SCOPE
1.1 This standard covers certain basic requirements regarding safe design,
installation, operation, te^ne and maintenance of ventilating systems with
respect to general ventilation and wherever appropriate dilution ventila-
tion for industrial process. This standard also briefly describes measures
to reduce the heat hazards due to industrial processes.
2. TERMINOLOGY
2.0 For the purpose of this standard, the following definitions shall apply.
2.1 Air Change per Hour — The volume of outside air allowed into a
room in one hour compared with the volume of the room.
2-2 Aarial Flow Fan — A fan having a casing in which the air enters and
leaves the inipellcr in a direction substantially parallel to its axis.
2 J Capture Velocity — Air velocity at any point in front of the exhaust
hood necessary to overcome opposing air currents and to capture the
contanUnated air at that point by causing it to flow into the exhaust hood.
2.4 Centrifugal Fan — A fan in which the air leaves the impeller in a
direction substantially at right angles to its axis.
23 Contandboauts^^ Dusts, fumes, gases, mists, vapours and such other
substances present in air are likely to be injurious or offensive to the
occupants.
2.6 PUution Ventilatioo — Supply of outside air to reduce the air-borne
concientration of contaminants in the building.
2.7 Dry Bidb Temperature — The temperature of the air read on a
thermometer, placed in such a way as to avoid errors due to radiation.
*Rulcs for rounding off numerical values ( revised).
4
tS : 3103 - 1975
2*8 Exhaust of Air — Removal of air fromr a building and its disposal
outside by means of mechanical device, such as a fan.
2.9 General Ventilation — Supply of outside air either by positive
ventilation or by infiltration into the building.
2.10 Humidification — The process whereby the absolute humidity of
the air in a building is maintained at a higher level than that of outside air
or at a level higher than that which would prevail naturally.
2-11 Humidity Absolute — The weight of water vapour per unit volume.
2.12 Humidity Relative — The ratio of the actual to the partial pressure
of the water vapour at the same temperature.
2.13 Local Exhaust Ventilation — Ventilation effected by exaust of air
through an exhaust appliance, such as hood with or without fan located as
closely as possible to the point at which contaminants are released so as to
capture effectively the contaminants and convey them through ducts to a
safe point of dispharge.
2.14 Make Up Air — Outside air supplied into a building to replace the
air removed.
2.15 Mechanical Ventilation — Supply of outside air either by positive
ventilation or by infiltration by reduction of pressure inside due to exhaust
of air, or by a combination of positive ventilation and exhaust of air.
2.16 Natural Ventilation — Supply of outside air into a building through
window or other openings due to wind outside and convection effects
arising from temperature or vapour pressure differences ( or both ) between
inside and outside of the building.
2.17 Positive Ventilation — The supply of outside air by means of a
mechanical device, such as a fan.
2,1'8 Propeller Type Fan — A fan in which the air leaves the impeller in
a direction substantially parallel to its axis designed to operate normally
under free inlet and outlet conditions.
2.19 Spray-head Systems — A system of atomizing water so as to
introduce the moisture directly into a building.
2.20 Temperature Rise — Difference of exit temperature and the
temperature of air at the inlet openings*^
2.21 Threshold Limit Values (TLV) — Refers to air-borne concentra-
tion of contaminant and represent conditions, under which it is believed
that nearly all occupants may be repeatedly exposed, day after day, with- ,
out adverse effect.
IS : 3103 - 1975
2.22 Ventilation — Supply of outside air into, or the removal of inside
air from an enclosed space.
2.23 Wet Bulb Ten^erature — The steady temperature finally given by
a thermometer having its bulb covered with gauze or muslin moistened with
distilled water and placed in an air stream of not less than 4*5 m/s,
3. ORIENTATION OF BUILDINGS
3.1 Solar Load Factors — In the tropics orientation for minimum solar
load during summer should be the main criterion. Wherever appropriate,
orientation to avoid the solar heat during summer and to take the desir-
able'heat during winter should be preferred.
3.1.1 Wherever possible suitable sun-breakers have to be provided to cut
off the incursion of direct sunlight to prevent heat radiation and to avoid
glare.
4. DESIGN CONSIDERATION
4.1 General — Ventilation is required to supply fresh air for respiration,
to dilute inside air to prevent vitiation by body odours, to remove any
contaminants in air and to provide such thermal environments as will
assist in the maintenance of heat balance of the body in order to prevent
discomfort and injury to health of the occupants.
4.1.1 Respiration — Supply of fresh air to provide oxygen for the human
body forXelimination of waste products and to maintain carbon dioxide
concentration in the air within safe limits rarely calls for special attention
as enough outside air for this purpose normally enters the areas of occu-
pancy through crevices and other openings.
4.1.2 Vitiation by Body Odours — Where no contaminants are to be
removed from air, the amount of fresh air required for dilution of inside
air to prevent vitiation by body odours, depends on the air space available
per person and the degree of physical activity; the amount of air decreases
as the air space per person increases, and it may vary from 20 m* to 30 m'
per person per hour. In rooms occupied by only a small number of person
such an air change will automatically be attained in cool weather by
normal leakage around windows and other openings and this may easily
be secured in warm weather by keeping the openings open.
4*1.2.1 Recommended values for air changes — No standards have been
laid down under the Factories Act (1948), as regards the aniount of fresh
air required per worker or the number of air changes per hour. Section
16 relating to overcrowding requires that at least 14 m' to 16 m* of space
shall be provided for every worker and for the purpose of that section no
account shall be taken of spaces in a work room which is more than 4*25 m
above the floor level.
lS:dl03-1975
4.1.2.2 The minimum fresh air required in a work room where there
are no contaminants to be removed from air, shall be such as to effect at
least three air changes per hour,
4.1.3 Heat Balance of Body — Specially in hot weather, when thermal
environment inside the room is worsened by heat given off by machinery,
occupants and other sources, the prime need for ventilation is to provide
such thermal environment as will assist the maintenance of heat balance of
the body in order to prevent discomfort and injury to health. Excess of
heat from a hot environment has to be offset to maintain normal body
temperature ( 37°C ). Heat exchange of the human body with respect to
surroundings is determined by temperature and humidity gradient between
the skin and surroundings, and therefore depends on air temperature ( dry
bulb temperature ), relative humidity ( or wet bulb temperature ), radia-
tion from the surroundings and air movement. The volume of outside
air to be calculated through the room is, therefore, governed by the
physical considerations of controlling the temperature, air distribution or
air movement.
4*1«3.1 Proper air movement and fresh 2iir supply will reduce heat
stress by dissipating heat from body by evaporation of the sweat particu-
larly when relative humidity is high and the air temperature is below or
near body temperature. Aar movement and distribution may, however,
be achieved by recirculation of the inside and/or outside air.
4.1.3.2 In industrial buildings where workers wearing light clothing
are expected to do work of moderate severity with the energy expenditure
in the range 235 to 330 kcal/h, the maximum wet bulb temperature shall
not exceed 29°C and adequate air movement subject to a minimum of air
velocity of 30 m/min shall be provided; and in relation to the dry bulb
temperature, the wet bulb temperature of air in the work room as far as
practicable, shall not exceed to that given in Table 1 .
4.2 Control of Heat — Although it is recognised that ventilation is one
of the most effective methods of controlling the thermal conditions in
factories, in many situations, the application of ventilation should be
preceded by and considered along with some of the following other methods
of control. This would facilitate better design of ventilation systems and
also reduce their cost.
4.2.1 Isolation — Sometimes it is possible to locate heat producing
equipment, such as furnaces in such a position as would expose only a
small number of workers to hot environments. As far as practicable
such sources of heat in factories should be isolated.
4.2«1«1 In situations where relatively few people are exposed to severe
heat stress and their activities are confined to limited areas as in the case
of rolling mill operators and crane operators, it may be possible to enclose
the work areas and supply conditioned air to such enclosures.
IS : 3103 - 1975
TABLE 1 MAXIMUM PERMISSIBLE WET BULB TEMPERATURES
FOR GIVEN DRY BULB TEMPERATURE
( Clauses ^.U3.2, 4.3.3 and 43 A )
Day Bulb
Tbmpebatuke, °C
Maximum Wet Bulb
Tbmpkratukb, **C
30
29-0
35
28-5
40
280
45
27-5
50
27-0
Note 1 — The limits indicated in the table are based on the upper safe limits
recommended in the report Thermal Stress on Textile Industry ( Report No. 1 7 )
issued by the Chief Adviser Factories, Government of India, Ministry of Labour and
Employment, New Delhi; these are limits beyond which the industry should not allow
the thermal conditions to go for more than one hour continuously. The limits arc
based on a series of studies conducted on Indian subjects in a psychrometric chamber
and on other data on heat casualties in earlier studies conducted in Kolar Gold Fields
and elsewhere.
Note 2 — Figures given in the table arc not intended to convey that human eflSciency
at 50*0 will remain the same as at 30*'C provided appropriate wet bulb temperatures
are maintained. Efficiency decreases with rise in the dry bulb temperature for a
given wet bulb temperatures attained and efforts should be made to bring down the
dry bulb temperatures as Well, as much as possible. Long exposures to temperature
of 50*C dry bulb/27*C wet bulb may prove dangerous.
Note 3 — ■Refrigeration or other naethod of cooling is reconmiended in all cases
where conditions would be worse than those shown in this table.
4*2»2 Ihsulatian — A considerable portion of heat in many factories is
due to the solar radiation falling on the roof surfaces, which in turn
radiate heat inside the factories. In such situations, insulation of the roof
or providing a false ceiling or double roofing would be very effective in
controlling heat. Some reduction can also be achieved by painting the
roof in heat reflective shades.
Hot surfaces of equipments, such as pipes, vessels, etc in the factory
should also be insulated to reduce their surface temperature.
4.2«3 Substitution — Sometimes, it is possible to substitute a hot process
by a method that involves application of localised or more efficiently
controlled method of heating. Examples include induction hardening
instead of conventional heat treatment, cold rivetting or spot welding
instead of hot rivetting, etc.
4«2*4 Radiant Shielding — Hot surfaces, such as layers of molten metal ema-
nate radiant heat which can best be controlled by placing a shield having a
8
IS: 3103 1975
lighly reflecting surface between the source of heat and the worker so
hat a major portion of the heat falling on the shield is reflected back to
he source. Surfaces, ^uch as, of tin and aluminium have been used as
materials for shields. The efficiency of the shield does not depend on its
thickness but on the reflectivity and emissivity of its surface. Care should
be taken to see that the shield is not heated up by conduction and for this
purpose adequate provision should be made for the free flow upwards of
the heated air between the hot surface and the shield by leaving the
necessary air space and providing opening at the top and the bottom of
the si^es.
4.3 Ventilation of Buildings — In the case of an industrial building
having a significant internal heat load due to manufacturing processes, the
following items may be considered when designing for the maximum
possible control of thermal environment:
a) Orientation of the building with respect to the direction of the
prevailing winds and of the path of the sun in the sky and to the
location of adjoining buildings.
b) Configuration of the building and the manufacturing processes
in it,
c) Proper inlets (windows and other openings) and their location
with respect to outlet openings.
d) Mechanical ventilation including selection and disposition of fans,
inlet grilles and arrangement of ducts.
In the case of industrial buildings wider than 30 m, the ventilation
may be augmented by roof ventilation.
4*3.1 The volume of air required shall be calculated by u§ing both the
sensible heat or latent heat as the basis. The lai^cr of the two figures
obtained should be used in actual practice.
4«3»1*1 Volume of air required for removing sensible heat when the
amount of sensible heat given off by different sources namely the sun, the
manufacturing processes machinery, occupants and other sources is known
and a suitable value for the allowable tenaperature rise is assumed, the
volume of outside air to be provided for removing the sensible heat m.ay
be calculated from:
n 3-462 X K,
where
0,1 == quantity of air in m*/h,
JTg == sensible heat gained in kcal/h, and
t =r allowable tem.perature rise in °&
18:314)3-1975
4.3.1.2 Temperature rise refers mainly to the diflference between the
air temperature^ at the outside and at the inlet openings. As very little
data exist on allowable temperature-rise values for supply of outside air
in summer months, the values given in Table 2 related to industrial
buildings may be used for general guidance.
TABLE 2 ALLOWABLE TEMPERATURE-RISE VALUES
{ Clauses 4.3.1.2 anrf 4.3.4 )
Height of Outlet Tkmpkrature Rise
Openings
6 3 to 4-5
9 4-5 to 6-5
12 fi-5to 11
Note I — The conditions arc limited to light or medium heavy manufacturing pro-
cesses, freedom from radiant heat and inlet openings not more than 3 to 4*5 m above
floor level.
Note 2 — At the working zone between floor level and 1*5 m above floor levels the
recommended maximutn allowable temperature rbe for air is 2 to 3**C above the air
temperature at the inlet openings.
4.3.1.3 Volume of aif required for removing latent heat — If the latent
heat gained from the manufacturing processes and occupants is also
known and a suitable value for the allowable rise in the vapour pressure
is assumed:
4 800 X ki
0.2 = -^
where
0,2 = quantity of air in m'/h,
^1 = latent heat gained in k cal/h, and
h — allowable vapour pressure difference in mm of mercury.
Note — • In majority of the cases the sensible heat gain will far exceed the latent
heat gain so that the amount of outside air to be drawn by ventilating equipment can
be calculated in moit cases on the basis of the equation given in 4.3.1.1.
4.3.1.4 Ventilation is also expressed as m^h/m* of floor area. This
relationship fails to evaluate the actual heat relief provided by a ventila-
tion system, but it does give a relationship which is independent of build-
ing height. This is a more rational approach because, with the same
internal load, the same amount of ventilation air, properly applied to the
\0
IS : 3103 - 1975
work zone with adequate velocity, will provide the desired heat relief
quite independently of the ceiling height of the space, with few exceptions.
Ventilation rates of 30 to 60 m^h/m' have been found to give good results
in many plants.
4.3.2 Natural Ventilation — The rate of ventilation by natural means
through windows or other openings depends on:
a) direction and velocity of wind outside and size and disposition of
opening (wind action), and
b) convection effects arising from temperature or vapour pressure
difference (or both) between inside and outside the room and the
difference of height between the outlet and inlet openings (stack
effect).
4.3.2.1 By wind action
a) Inlet openings in the building should be well distributed and
should be located on the windward side at a low level and outlet
openings should be located on the leeward side near the top so
that incoming air stream is passed over the occupants. Inlet and
outlet openings at high level may only clear the top air without
producing air movement at the level of occupancy. When outlets
serve as inlets, they shall be located at the same level.
b) Inlet openings should not, as far as possible, be obstructed by
adjoining buildings, trees, signboards or other obstructions or by
inside partitions in the path of air flow.
c) Greatest flow per unit area of openings is obtained by using inlet
and outlet openings of nearly equal areas.
d) Where the stream of wind is quite constant and dependable the
openings may be readily arranged to take full advantage of the
wind. Where the wind direction is quite variable, the openings
shall be arranged so that as fai^,as possible there is approximately
equal areas on all sides and the openings be located at the same
levels. Thus no matter what the wind direction is, there are
always some openings directly exposed to wind pressure and others
to air s,uction and effective movement through buildings is assured.
4.3.2*2 By stack effect — Natural ventilation by stack effect occurs
when air inside a building is at a different temperature than air outside.
Thus in heated buildings or in buildings wherein hot processes are carried
on and in ordinary buildings during summer nights and during premon-
soon periods, the inside temperature is higher than that of outside, cool
outside air will tend to enter through openings at low level and warm air
will tend to leave through openings at high level. It would, therefore, be
advantageous to provide ventilators as close to ceilings as possible. Venti-
lators 'can also be provided in roofs as, for* example, cowl, vcntipipe,
covered roof and ridge vent.
11
rS : 3103 - 1975
4.3,3 Mechanical Ventilation, General — Where adequate air changes
specified in recommended values for air changes or for providing thermal
environment within the limits specified in Table 1 whichever is higher,
cannot be obtained by natural ventilation, mechanical ventilation either
by exhaust of air or by positive ventilation or combination of the two
shall be provided, and in case of positive ventilation where necessary, air
before being brought into the area of occupancy, may be cooled by
evaporative cooling or by air-conditioning.
4.3.3.1 Exhaust of air — Exhaust fans are provided in walls on one
side of the building or in the attic and roofs to draw large volumes of air
through the building. These fans are usually of propeller type since they
operate against little or no resistance. It is important that windows and
other openings near the fans are kept closed as otherwise the fans would
draw outside air from these openings and cause what is termed as ^short-
circuiting'. Adequate inlet openings shall be provided on opposite side
of the building so as to limit inlet velocities. When fans are centrally
located on an attic or other unused space and arranged to draw propor-
tionately from several work areas or from exhaust appliances with duct
work, these are predominantly centrifugal type or sometimes axial types
so as to overcome the resistance from duct work.
4*3*3«2 Positive ventilation — Positive ventilation is provided by
centrally located supply fans which are usually of centrifugal type having
a wide range of capacities and quiet operation. Considerable advantage
may be acliieved by incorporating the ducts into the building structure
and by having the interior surfaces carefully finished to render them
smooth and air-tight and treated to prevent the possibility of dust being
scoured from the walls by the passing air. Unit ventilators may be pro-
vided for individual rooms and may be placed against outside wall near
the central line of the room. Both central system and unit ventilators
could be equipped to provide, besides the function of ventilating, cooling
by evaporative cooling coils. Typical installations are equipped with
systems of controls that permits ventilating and cooling effect to be varied,
while the fans are operating continuously, in accordance with the room
requirements.
4.3.3.3 Combined systems — The combined systems with positive
ventilation and with exhaust of air have the advantage of providing better
control conditions and better distribution of air over the entire area of
occupancy particularly in wider buildings. By supplying proper volumes
of air at suitable velocities at the required areas through duct work and
by extracting the air in the return ducts and recirculating this air after
properly mixing it with cool fresh air, completely satisfactory ventilation
is obtained. In a combined system it is preferable to provide slight
excess of exhaust if there are adjoining occupied spaces and a slight excess
of supply if there are no such spaces. Unit exhausters can also be used
to match unit ventilators' exteriors and located along the outside wall.
12
18:3103-1975
4*3«4 Evaporative Cooling — In regions where high day-time temperatures
prevail with reasonably low humidities, evaporative cooling may be em-
ployed effectively to lower the temperature of the air to near the wet bulb
temperature and produce an air supply cool enough to take care of the
indoor sensible heat loads without exceeding the upper safe limits given in
Table 1 'or the temperature rise values at area of occupancy given in Note 2
in Table 2. By positive ventilation this air may be supplied to produce
cooler environments with lower air volume than would be required
under 4.3.1.1* The amount of air required as greater temperature rise than
given under Table 2 may be tolerated. Although the relative humidity
of supply air will be increased but due to the large sensible heat loads the
resultant relative humidity of the air will be. sufficiently lowered after
mixing with the inside air to produce body cooling.
4.3.4.1 Evaporative cooling with positive ventilation using a central
plant consisting of a water spray chamber and a fan to supply outside air
into the work room through a distribution duct is far preferable to spray
head system which only humidifies the'air, the cooling capacity of the air
will be very little improved; and none of the air which absorbs the heat
given off by machinery, manufacturing processes and occupants, is
removed from the building under these conditions,
4.3.4.2 Evaporative cooling is generally used where humidification . is
necessary to meet the requirements of manufacturing processes in factories,
as for instance, in a cotton mill to keep the textile fibres pliable and
strong in a rubber factory to prevent static electricity in processes using
volatile and inflammable solvents or in printing and lithographic works to
maintain accurately the size of the paper and other materials.
4.3.4.3 Where humidification or dehumidification is necessary to' meet
the requirements of manufacturing processes, the requirements shall be
ascertained from the clients. In respect of cotton spinning and weaving
factories, attention is drawn to the requirements regarding temperatures
and humidities under relevant rules framed by the State Government
under Section 15 of the Factories Act (1948).
4.3.5 Air-Conditioning — Where the desired temperatures and humidities
cannot be obtained by mere ventilation, air conditioning may be resorted
to {see IS : 659-1964* and IS : 660-1963t).
4.3.5*1 When refrigeration is employed to obtain desired temperature
inside a work room it may be necessary to circulate more air than that
required for ventilation purposes alone, and in that case, part of the air
may be recirculated to save refrigeration.
♦Specification for safety code for air-conditioning ( revised ).
^Specification for safety code for mechanical refrigeration ( revised ).
13
IS : 3103 - 1995
4.3.5.2 The proportion of recirculated air will depend on the circum-
stances but the quantity of fresh air taken in shall not be less than that laid
down under 4.1 •2*1 or that required as make-up air to replace the air
exhausted for control of air contaminants {see 4.5) whichever is higher.
4.3.6 Fresh air shall be free from organic matter and deleterious
inorganic dust and fume, and should be drawn from areas where the air
is not likely to be polluted or vitiated; where necessary, the air should be
efficiently filtered.
4.4 Air Distribution — In providing ventilation, proper consideration
should be given to size and distribution of windows and other inlet open-
ings in relation to outlet openings arrangement of ducts and selection and
disposition of fans and air intake grilles so as to give, with due regard to
orientation, prevailing winds, configuration of the building and manufac-
turing processes carried on, maximum possible control of thermal environ-
ments in the work rooms. Air should be distributed evenly without dead
air pockets or undue draughts caused by high inlet velocities. When
ventilation is provided by infiltration due to exhaust of air, it is important
that windows and other openings near the fans are kept closed as other-
wise the fans would draw outside air from these openings and cause what
is termed 'short circuiting'.
4.4.1 Air Movement — The rate of air movement in the vicinity of
workers shall be such as to give reasonable comfort without objectionable
draughts. In general, velocity of air excess of 60 m/min should be
avoided unless the temperatures and humidities are high.
4.4.1*1 Where heavy manual work is performed by workers, a greater
degree of air movement may be desirable depending upon the tempera-
ture and humidity of air. When the nature of the manufacturing pro-
cesses demands conditions of temperature and humidity which are above
the normal range of comfort, the question of rate of air movement requires
critical examination, particularly if the dry bulb temperature is above
that of body. If the air is capable of absorbing heat from the body a
blast of air up to 300 m/min may be directed at the workers for velocity
cooling.
4.5 Ventilation for Control of Air Contaminants
4.5.1 Local Exhaust Ventilation — When in a work room by reason of
manufacturing processes contaminants are given off, it shall be necessary
to provide an efficient local exhaust ventilation of the points at which the
contaminants are released to reduce their concentration in the working
area below Threshold Limit Values (TLV) {see 0.4) . Such points shall,
as far as possible, be enclosed, but if it is necessary to have an access while
the manufacturing processes are carried on, the exhaust appliance shall
14
IS: 3103 -1975
confine the contaminants as much as possible and openings for access shall
be located, wherever possible, away from the natural path of the contami-
nants travel.
4.5.1.1 When an exhaust appliance is provided to enclose the point
at which contaminants are released, the volume of air required is cal-
culated from the area of openings and the capture velocity sufficient to
prevent outward escapement. In other cases, the volume of air required
and pattern of air flow in front of the exhaust appliance shall be such that
the capture velocities necessary to overcome air currents and convey the
contacminants by causing the air recommended capture velocities arc
listed out in Table 3.
TABLE 3 RANGE OF RECOMMENDED CAPTURE VELOCITIES
Sl
No.
(1)
ii)
iii)
iv)
Condition of Dispersion
OF Contaminant
(2)
Released with practically no
velocity into quiet air
Released at low velocity into
moderately still air
Active generation into zone
if rapid air motion
Released at high initial velo-
city into zone of very rapid
air motion
EXAMFLBS
(3)
Capture Velocity
Evaporation from tanks
degreasing etc
Spray booths; intermittent
container filling, low
speed conveyor transfers;
welding; plating; pickling
Spray painting in shallow
booths; barrel filling;
conveyor loading; crushers
Grinding: abrasive blasting,
tumbling
(4)
m/s
0-25-0-5
0-5-10
1-0-2 -5
2*5-iO
4*5*1 .2 The sizes of the ducts shall be determined considering the
volume of air required and duct velocities necessary to convey the con-
taminants with minimum possible static resistance consistent with the
economics of installation and operation. Fan shall be of such type and
size as to move the required volume of air and overcome the total resis-
tance of the local exhaust ventilation system including the air cleaning
devices.
4*5*2 Dilution Ventilation — Dilution ventilation is employed to reduce
the concentration of contaminants in the working area below the Thres-
hold limit Values (TLV) when the contaminants are of low toxicity with
TLV above 100 ppm (parts per million by volume) and the quantity of
contaminants generated is not high (such as vapours given off by organic
solvents of low toxicity). However, dilution ventilation is not as satis-
factory for control of air contaminants as is local exhaust ventilation.
15
IS: 3103 -1975
4«5«2*1 The exhaust outlets and the air supply inlets shall be so located
that air passes through the zone of contamination with the points at which
the contaminants are released between the worker and the exhaust outlets.
The workers should not stand too close to the zone where contaminants
are released.
4.5.2*2 If the rate of vapour generation of rate of liquid evaporation
is known, the dilution air requirements is calculated from:
Air required in m^/kg 24 X 10« X A:
of evaporation —
molecular weight of liquid X TLV
where
k = constant varying from 3 to 10 depending on solvent in
question, uniformity of air distribution, dilution of vapours
in air, location of exhaust plant and its proximity to
evolved vapours, and
TLV = Threshold Limit Value of the solvent
4.5*3 Make^Up-Air — Sufficient make-up-air shall be brought into the
work room by natural infiltration or by positive ventilation at suitable
points in relation to the exhaust points to replace the air exhausted by
local exhaust ventilation or by dilution ventilation, and the air may be
efficiently filtered or treated, when necessary*
5. INSTALLATION AND OPERATION
5.1 Location — Fans and other equipment may be located in convenient
positions considering the intake of fresh air, accessibility for maintenance
and noise control.
5»1.1 Where the exhaust of air laden with inflammable dusts, gases or
vapours is conveyed through ducts, the electric motor and fan shall be
situated outside in such a way that an explosion will not vent into the
work room. The fan should be of non-sparking construction and the
motor, if not located outside the air stream, should be of flame proof
construction.
5*2 I>ucts — Where positive ventilation requires ducts for proper air
distribution considerable advantage may be achieved by incorporating the
ducts into the building structure and by having the interior surfaces care-
fully finished to render them smooth and air-tight and treated to prevent
the possibility of dust being scoured from the walls by the passing air.
For removal of corrosive or dust laden contaminants, ducts shall be pro-
tected against corrosion and erosion and shall be installed for easy
inspection, maintenance, repair and replacement,
5.2.1 Where metal duct work is installed, it shall conform to IS : 655-
1963*.
^Specification for metal air ducts ( revised),
16
IS: 3103 -1975
5.3 Noise — Where in a work room owing to the nature of manufacturing
processes carried on, noise supression is important, close attention shall be
given to the design and installation of motors, fans and ducts to ensure
quite operation and to minimize transmission of noise.
5.4 The performance of ventilating equipment, such as fans and filters,
over a period of years is considerably influenced by the extent of
the initial provision of facilities for its efficient operation and maintenance.
The following points shall be borne in mind:
a) Adequate access for inspection, cleaning and repair of
component parts;
b) Reasonable space during operation;
c) Location of dampers and other operating controls in such a
position as would permit quick and easy operation; and
d) Adequate lighting and ventilation at places where the equipment
is to be operated and maintained.
6. TESTING
6-1 All parties concerned shall agree to the objects of test, methods and
duration of test, degree of accuracy required and state of ventilating
cquipm.ent under test. The plant shoiild be run during norm.al working
hours and adjusted properly ]:rior to the test.
6*2 Amount of Air
6.2.1 Positive Ventilation — The volume of outside air by positive ventila-
tion shall be measured by appropriate instruments, such as a properly
calibrated, 'anemometer', velocity* meter and pilot tube. To measure the
average velocity of £iir flow, it is ne^cessary to make a traverse of the
instrument over the cross*sectional area of the intake openings or ducts
and obtain the average velocity from these results. The volume of air is
given by:
where
Q^== volume of air in m'/mirt,
A = free area of intake openings of ducts in m^ and
V ~ average velocity of air in m/min.
6-2.2 Exhaust of Air — The volume of exhaust air shali be measured in
the same manner as in the case of positive ventilation by measurement of
air Velocity and area of exhaust ducts or openings, and multiplying the
one with the other.
17
IS: 3103 -1975
6.2.3 Natural /filtration — This is difficult to measure as it varies from
time to time. The amount of outside air by natural infiltration through
doors or windows or through other openings depends on direction and
velocity of wind outside and/or convection effects arising from temperature
of vapour pressure difference ( or both ) between inside and outside of the
work room.
6.2.3.1 Ventilation due to wind outside is given by the formula:
d^EAV
where
Q^= volume of air in m^niin;
A = free area of inlet openings in m^;
F— velocity of wind in m/min; and
E = co-efficient which varies from 0'5 to 0'6 whcit openings face
wind, and 0*25 to 0*35 when openings are at mi angle.
6«2.3.2 Ventilation due to convection effects arising from tempera-
ture difference between inside and outside is given by:
(1=. TO A^ h {tr - to)
where
Q. = volume of air in m/min;
A = free area of inlet openings in m^;
h = vertical distance between inlets and outlets in mm;
tr= average temperature of indoor air at the outlet, in ^'C; and
to = temperatur-e of outdoor air in °C.
Note — The equation is based on 0*65 efFrctivenc^s of openings. This should be
reduced to 0'50 if conditions are not favourable.
6.2.3«3 When areas of inlet and outlet openings are unequal, ^A' given
in equations under 6.2.3*1 and 6.2»3.2 will be the smaller area and the
volume of air will be increased according to the percentage given in Fig. 1.
6.2.3.4 Ventilation by combined effect of wind outside and tempera-
ture difference may be evaluated as follows:
a) Calculate the amount of outside air by methods given under 6.2.3.1
and 6.2.3.2,
b) Express the amount of air due to method 6.2.3.2 as a percentage
of the total, and
c) Use Fig, 2 to determine actual fl6w caused by the combined effect
of both.
18
is : 3103 • 1975
40
^MM
■■
•-
>
y^
^
J
/
Z tn
/
^
i
^ in
1
^ "
1
L_
u
t
P"^
^
6
Fig. I
ratio of outlet to inlet or vice -versa
Increase in Flow Caused by Excess of One
Opening Over Another
7
§W 6
IL Z
*t.
tV
gr
!5$ -i
L
V
\
^
H
9S ^
0
1
har
J-3
r
h
r
4
BT
Ho
Fig. 2
FLOW DUE TO TEMPERATURE
CNFFEREtK AS PERCENT OF TOTAL
Determination of Flow Caused by Combined Forces of
Wind and Temperature Difference
6.2.4 Combined Effect of Different Methods of Ventilation — When combina-
tion of two or more methods of general ventilation is used, the total rate of
ventilation shall be reckoned ?s the highest of the following three:
a) rate of positive ventilation {see 6.2.1 ),
b) rate of exhaust air ( see 6*2«2 ), and
c) 1*25 times the rate of natural infiltration ( see 6.2.3 ).
This rule shall be followed until an exact formula is established
by research.
19
IS: 3103- 1975
6.3 Air Movement — Turbulent air movement at the working zone may
be measured either by Kata thermometer (dry silvered type), heated
thermo anemometer or properly calibrated thermocouple anemometer.
Kata thermometer and heated thermometer give cooling, power rather
than the velocity of air, and the rate of air movement is found out
from the cooling power by reference to a nomogram using the ambient
temperature.
6.4 Tolerances — The rate of air flow as measured in the duct or at a
grille either by positive ventilation or exhaust of air shall be within
10 percent of the amount required.
6.4.1 Variation of air flow through filters and grilles shall not at any
time be more than db 20 percent of the mean value.
7. MAINTENANCE
7.1 All ventilating equipment shall be checked periodically and bearings
of various moving parts lubricated. The equipment shall also be tested
for air delivery. Such tests shall be made at least once in a year.
7.2 The surfaces of any cooling or heating units and air cleaning devices
( including filters ) shall be inspected at frequent intervals for corrosion
and dirt and when corrosion occurs the corroded parts shall be carefully
cleaned and protected with anti-corrosion paint or other suitable medium.
Cleaning of filters and heat transfer units shall be carried put regularly to
promote their efficient use.
8. SAFETY REQjUIREMENTS FOR ELECTRICAL EQUIPMENT
8.1 Electrical Equipment — Electrical wiring and installation of electrical
equipment shall be in accordance with the requirements of Indian Electri-
city Act f*nd Rules and shall also conform to IS : 732-1963* arid
IS : 2274-19631 as applicable.
8.2 Fire Safety — Due consideration shall be given to the* fire safety
aspects as given in IS : 1646-1961 J.
•Code of practice for electrical wiriiig iflstaUations (system voltage not exceeding
650 volts ) ( revised ) .
fCode of practice for electrical wiring installationi (system voltage exceeding
650 volts).
JCode of pi^ctice for fire safety of buildings (general ) electrical installations.
20
BUREAU OF INDIAN STANDARDS
Headquarters :
Mana|cJ|havan, 9 Bahadur Shah Zafar Marg, NEW DELH1 110002
Telephones : 331 01 31 Telegrams : i
33113 75 (Common
Regionai Offices :
Central ; Manak Bhavan, 9, Bahadur Shah Zafar Marg.
NEW DELH II 10002
•Eastern : 1/14 C.I.T. Scheme VII M,
V.I.P. Road, Maniktola, CALCUTTA 700054
Northern : SCO 445-446, Sector 35-C, CHANDIGARH 160036
Southern : C.l.t. Campus, IV Cross Road, MADRAS 600113
t Western : Manakalaya, E9 Ml DC, MaroL Andheri (East),
BOMBAY 400093
Brancfi Offices :
'Pushpak', Nurmohamed Shaikh Marg, Khanpur, AH MADABAD 380001
t Peehya Industrial Area, 1st Stage, Bangalore-Tumkur Road,
BANGALORE 560058 _^
Gangotrl Complex, 5th Floor, Bhadbhada Road, T.T. Nagar,
BHOPAL 462003
Plot No. 82/83, Lewis Road, BHUBANESHWAR 751002
Kalai Kathir Building, 6/48-A Avanasi Road, COIMBATORE 641037
Quality Marking Centre, N-H. IV, N-LT., FARIDABAD 121001
Savitri Complex, 116 G.T. Road, GHAZIABAD 201001
53/5 Ward No. 29, R.G. Barua Road, 5th By-lane,
GUWAHATI 781003 /
5-8-56C L. N. Gupta Marg, ( Nampally Station Road )
HYDERABAD 500001
R14 Yudhister Marg, C Scheme, JAIPUR 302005
117/418 B Sarvodaya Nagar, KANPUR 208005
Plot No. A-9, House No. 561/63. Sindhu Nagar, Kanpur RoaO,
LUCKNOW 226005
Pattiputra Industrial Estate, PATNA 800013
District Industries Centre Complex, Bagh-e-AII Maidan,
SRI NAGAR 190011
T. C. No. 14/1421, University P.O., Palayam.
THIRUVANANTHAPURAM 695034
inspection Offices (With Sale Point) :
Pushpanjali. First Floor, 205'A W^t High Court Road.
Shankar Nagar Square, NAGPUR 440010
Institution of Engineers (India) Building, 1332 Shivaii Nagar.
PUNE 411005
Manaksanstha
to all Offices)
Teiepfione
J 331 0131
Z331 13 75
37 86 62
218 43
41 2916
6 32 92 95
1 2 63 48
39 49 55
55 40 21
5 36 27
2 67 05
8-71 19 96
3 31 77
2310 83
6 34 71
21 68 76
5 55 07
•Sales Office Calcutta is at 5 Chowringhee Approach,
P. O. Princep Street, CALCUTTA
t Sales Office is at Novelty Chambers. Grant Road, BOMBAY
% Sales Office is at Unity Building, Narasimharaja Square,
BANGALORE
6 23 05
6 21 04
62 51 71
6 24 35
27 68 00
89 66 28
22 39 71
Reprography Unit, BIS, New Delhi, India